|

FIGURE 1.
SUGGESTED CONTROL
JOINT LOCATIONS
|
|

FIGURE 2.
SUGGESTED LOCATIONS AND
SPACING FOR CONTROL JOINTS IN CMU
WALLS
|
Design for Movement
Control
In California, the majority
of structural concrete masonry walls are fully
grouted; thus the shrinkage calculations are more
complex as compared to ungrouted walls.
The linear drying shrinkage
of units, along with strength and ingredients of
grout acting together, makes calculations not only
tedious, but also with lesser degree of
reliability.
Under the most ideal
assumption of all components (units, mortar and
grout) behaving as a unit, it is possible to
calculate strains in masonry and design horizontal
reinforcement to limit crack widths to less than
0.020 inches (a number considered acceptable for
long-term behavior of wall). However, such
calculations are based on the tensile strength of
mortar, grout and units, which are not only
different, but also have a high degree of
variability. (A typical value for tensile strength
of masonry units is 200 psi, whereas that of a head
joint is 25 psi. Taking an average of two values is
questionable, although simple.)
To resist seismic shear,
considerable amount of horizontal reinforcement is
provided in concrete masonry walls. Such
reinforcement resists shrinkage, however, one needs
to use judgement. If the reinforcement is stretched
to prevent shrinkage cracks, sufficient capacity
may not be available to resist seismic
shear.
Due to the uncertainties
associated with the calculations of reinforcement
for shrinkage resistance, it is perhaps desirable
to use an empirical approach to provide control
joints.

FIGURE 3. MASONRY
CONTROL JOINT
DETAILS
|
|



FIGURE 4. CONTROL
JOINT ELEVATION
AND
|
FIGURE 5. DOWEL
ACROSS JOINT
|
Empirical Design (UBC and
NCMA Comparisons)
Based upon the historical
data over many years in different geographical
conditions, National Concrete Masonry Association
(NCMA) has developed the following criteria for
control joints.
The Spacing of control joints
should be the lesser of:
|
a.
|
25 feet or
|
|
b.
|
Length to height
ratio of 1.5.
|
If a wall were 22 feet high,
the governing spacing would be 25 feet, since based
upon "b," the spacing would be 33 feet.
The empirical criteria is
based upon assumption of minimum horizontal
reinforcement of 0.025 in2/ft height of
the wall.
If we consider a typical
8-inch thick concrete masonry wall and provided
horizontal reinforcement spaced at 48 inches, the
required area would be
4 x 0.025 = 0.10 in2.
Thus, for shrinkage control
only, we need to provide 2-¼ diameter wires in
the mortar joint. However, in California, based on
the 1997 UBC, the minimum horizontal reinforcement
requirement is 0.0007 bt. and the minimum size of
reinforcement is #3 (except that joint
reinforcement can be smaller). The spacing of bars
cannot exceed 48 inches. Whereas the minimum
horizontal reinforcement requirement in the UBC is
based upon the volume of masonry, NCMA empirical
requirements are not based upon the total volume,
since most of the country uses ungrouted
masonry.
Perhaps, in ungrouted
masonry, surface area is more relevant as compared
to volume.
The following table compares
minimum required horizontal reinforcement per UBC
provisions and NCMA TEK 10-2B for 48 inch
spacing.
TABLE 1
|
Wall Thickness
inches (actual)
|
As(in2/ft)
(0.0007 bt.)
|
UBC
|
NCMA
|
|
6
(5.625)
|
0.047
|
0.188
|
0.10
|
|
8
(7.625)
|
0.064
|
0.256
|
0.10
|
|
10
(9.625)
|
0.081
|
0.324
|
0.10
|
|
12
(11.625)
|
0.098
|
0.392
|
0.10
|
It is clear from a quick
review of the table that minimum UBC requirements
for horizontal steel exceed those required to
control shrinkage cracks.
In projects where minimum
horizontal reinforcement requirement governs, the
shrinkage control requirement needs are already
met.
Horizontal
Reinforcement
The following approach is
suggested to compute total horizontal reinforcement
needed.
|
·
|
Add 0.025
in2/ft to that required by
design. If the ratio is still below 0.0007
bt., use the minimum required. If the
ratio is more than 0.0007 bt. use that
ratio, however for total reinforcement
requirement in the wall, deduct only
0.0007 bt.
|
|