Spring 2002
DESIGN
OF MASONRY PIERS
INTRODUCTION
Masonry piers typically occur in shear walls
that have perforations such as openings for doors
or windows. Their design is similar to the design
of walls and columns. However, because of the
geometric configuration of piers, there are certain
aspects of the design that warrant further
discussion. This issue of "Masonry Chronicles" will
study the design of piers and provide an example
that illustrates the strength design procedures of
the 1997 Uniform Building Code (UBC). The issues
that will be discussed are as follows:
|
|
·
|
Distribution of lateral loads to
adjacent piers
|
|
|
·
|
Design of piers for in-plane forces
|
Distribution of Lateral Loads to
Piers
Lateral loads are distributed to piers in
proportion to their stiffnesses or rigidity. Thus
calculations need to be performed to obtain the
relative stiffnesses of the piers in a wall.
For a pier that is fixed against rotation at the
top and bottom supports, the displacement,
" ,"
due to a lateral force, F is given by the following
equation:

(1)
where E is the modulus of elasticity,
G is the shear modulus, h is the
height of the pier, and A and I are
the area and moment of inertia of the pier cross
section, respectively. For masonry, we can assume
that G = 0.4E. Then, using the
appropriate relationships for the pier geometric
properties:

where L and t are the length and
thickness of the masonry pier, respectively, the
displacement a pier subjected to a unit load at the
top is given by:
 (2)
Since we are only concerned with the
relative stiffness of the piers, we
can assume arbitrary values for E and t. Assuming
that E = 1 and t = 1, the relative
rigidity, R, of each masonry wall, which is
the inverse of the displacement due to a unit load,
is given by:
 (3)
For a cantilever pier, which is free to rotate
at the top, the corresponding rigidity is given
by:
 (4)
Design for In-Plane Loads
The design of piers subjected to in-plane forces
is similar to the design of columns and walls in
that they are considered as elements that resist
both in-plane axial loads and in-plane flexural
loads. The strength design provisions of the 1997
UBC stipulate specific constraints on the
dimensions and reinforcement details of piers. It
is the author's recommendation that piers designed
using the working stress method also adhere to
these requirements.
Dimensional Limits (Section
2108.2.3.9)
|
|
·
|
The nominal width of a pier shall not
be less than 6 inches
|
|
|
·
|
The distance between lateral supports
of a pier shall not exceed 30 times the
nominal width of the pier except as
provided for below:
|
|
|
|
1.
|
When the distance between lateral
supports of a pier exceeds 30 times the
nominal width of the pier, the provisions
of Section 2108.2.4 (Wall design for
out-of-plane forces) shall be used for
design.
|
|
|
·
|
The nominal length of a pier shall not
be less than three times the nominal width
of the pier and shall not be greater than
six times the nominal width of the
pier.
|
|
|
·
|
The clear height of a pier shall not
exceed five times the nominal length of
the pier, except that the length of a pier
may be equal to the width of a pier when
the axial force at the location of maximum
moment is less than 0.04 f
'mAg.
|
Reinforcement Details (Section
2108.2.3.11)
|
|
·
|
A pier subjected to in-plane stress
reversals shall have symmetric
longitudinal reinforcement.
|
|
|
·
|
At least one longitudinal bar shall be
provided in the end cells
|
|
|
·
|
The minimum longitudinal reinforcement
ratio shall be 0.0007
|
|
|
·
|
Transverse reinforcement shall be
provided when the factored shear, which is
based on the Maximum Inelastic Response
Displacement, exceeds shear capacity of
the masonry alone.
|
|
|
·
|
The minimum transverse reinforcement
ratio shall be 0.0015
|
|
|
·
|
Shear reinforcement shall be hooked
around the extreme longitudinal bars with
a 180-degree hook. Alternatively, at wall
intersections, transverse reinforcement
with a 90-degree standard hook around a
vertical bar in the intersecting wall
shall be permitted.
|
Note also that Section 2108.2.3.11.1 stipulates
that the factored axial compression on piers shall
not exceed 0.03Ae f
'm
Design Example
The wall shown in Figure 1 resists a lateral
earthquake load of 50 kips.
|
|
·
|
Calculate the shear in the wall
piers
|
|
|
·
|
Design Pier 3 for the calculated in
plane earthquake forces assuming the
building is located at a site with a
seismic coefficient Ca =
0.48.
|
Materials
Masonry: 8-inch thick normal weight (84 psf)
fully grouted f 'm =1500 psi
Reinforcing Steel: Grade 60

Figure 1
Example Masonry Wall with Piers
Distribution of Lateral Loads to
Piers
All piers except Pier 1 can be considered as
fixed against rotation at the top and bottom. Table
1 provides the calculations for the rigidities of
the various piers.
Table 1 Relative Rigidities of Piers
|
|
h
|
L
|
h/L
|
R
|
|
1
|
4.0
|
20.0
|
0.20
|
1.58
|
|
2
|
7.3
|
2.7
|
2.70
|
0.04
|
|
3
|
4.7
|
4.0
|
1.18
|
0.19
|
|
4
|
4.7
|
3.3
|
1.42
|
0.14
|
|
7
|
2.7
|
12.0
|
0.23
|
1.46
|
For piers that are in parallel the total
rigidity is equal to the sum of the individual pier
rigidities:
 (5)
For piers that are in series the relationship
for total rigidity is given by:
 (6)
where A and B are two piers.
The load in each pier is calculated by
considering the load path of the lateral load at
the top of the wall. At the top of the wall, Pier 1
resists the entire load. Thus:
Vu1 = 50 kips
At the window opening level, load is distributed
between Pier 2 and the combination of Piers 3, 4
and 5.
R2 = 0.04

Therefore the shear in the various piers is
equal to:
kips
kips
Similarly, the shear in Piers 3 and 4 are given
by:
kips
kips
kips
Design Pier 3 for In-Plane Loads
The load combinations to be considered for
earthquake loads are as follows
1.2D + E
0.9D + E
where E = Eh ±
Ev and Ev is equal
to 0.5CaID. Note that the 1.1
factor in Section 1612.2.1 of the 1997 UBC is not
included in the load combinations, as recommended
by the Structural Engineers Association of
California (SEAOC). The load combination then
becomes :
1.2D + Eh +
0.5(0.48)(1.0)D = 1.44D +
Eh
0.9D + Eh -
0.5(0.48)(1.0)D = 0.66D +
Eh
Figure 2 shows the tributary area of the pier
for gravity loads. The first load combination,
which represents the maximum axial load, is
evaluated at the bottom of the pier. The axial load
is thus
lbs
The second load combination, which represents
the minimum axial load, is evaluated at the top of
the pier. The axial load for this load combination
is equal to:
lbs
The bending moment for both load combinations is
equal to
kip-ft
Figure 2
Tributary Area for Pier 3 Gravity Loads
Figure 3 shows a cross-section of the pier with
the longitudinal wall reinforcement. The selected
design will now be checked to see if it can resist
the required loads.
Figure 3 Selected Reinforcement for
Pier
To obtain the moment capacity of the pier under
various axial loads, an axial load-moment
interaction diagram of the wall with the selected
reinforcement has to be created. For simplicity,
three control points will be located on the
interaction diagram (see Figure 6). This is a
conservative approximation, and a more accurate
is a conservative approximation, and a
more accurate curve can be obtained by calculating
more points on the interaction diagram.
With no moment on pier (Control Point 1) the
nominal axial load capacity of the pier is given by
(Section 2108.2.1.2):

From Section 2108.1.4.1, the capacity reduction
factor is given by:

Therefore
= 0.6. For Control Point 2, which has no axial
load, we iterate to obtain the neutral axis of the
section so that the sum of vertical forces equals
zero. A rectangular compressive stress block, with
a maximum usable compressive strain of 0.003 is
used for the masonry, as stipulated in Section
2108.2.1.2 of the UBC. Figure 4 shows that the
depth of the neutral axis for this condition is
equal to 4.24 inches.
Figure 4 Strain and Stress on Pier with no
Axial
Load (Control Point 2)
Taking moments about the centerline of the
pier:

The capacity reduction factor at this axial load
is equal to 0.80.
At the balanced strain condition (Control Point
3), the strain in the extreme compressive fiber is
equal to 0.003 and the extreme reinforcing steel is
just yielding as shown in Figure 5. The depth of
the neutral axis from the extreme compression fiber
cb is given by:
in
Checking the equilibrium of the wall
cross-section with the given neutral axis location,
the balanced axial load is found to be 218 kips and
the balanced moment is 274 kip-ft. The capacity
reduction factor is equal to 0.6 at the balanced
condition. Figure 6 shows the interaction diagram
for the wall using the three control points
obtained. The Figure also shows that the section is
adequate for the combined axial load and bending
moment at both load combinations.
Figure 5 Strain Profile at Balanced
Strain Condition
Figure 6 Interaction Diagram for
Pier
Section 2108.2.3.11.3 stipulates that piers
should be designed to resist the shear at the
Maximum Inelastic Response Displacement, m.
One way to satisfy this design criterion is to
design the wall to resist the maximum shear that
can be developed based on the moment capacity of
the pier.
For the example being considered here, the
nominal moment capacity at the maximum axial load
of 7.4 kips is equal to:
kip-ft
and the corresponding shear is:
kips
If we try #5 bars spaced at 16-inches on center
for the transverse reinforcement, the transverse
reinforcement ratio is equal to:

The shear capacity is given by:

= 42.3 kips OK
Conclusions
The design of piers is similar to the design of
walls and columns, with the additional requirement
that the relative rigidities of piers need to be
calculated in order to distribute the lateral loads
to the various piers in a wall. The shear demand on
a pier is dependent on the moment capacity. It is
therefore disadvantageous to over design a pier by
providing excessive flexural reinforcement since
this only increase the amount of transverse steel
that is required to resist the shear demands.
This issue of "Masonry Chronicles" was
written by Dr. Chukwuma Ekwueme of the Hart
Weidlinger Group.
Errata for "Winter 2001-2002" issue:
Under "Construction" item e.4 add,
"grout
pours greater than 12 inches shall be
re-consolidated by mechanical vibration."
Errata for "Spring/Summer" issue:
under Typical Proportions for Mortar, "Type M"
should read "Type S" and vice versa.
|