|
COMPARISON OF THE 1997
UBC AND THE 2002 MSJC CODE
INTRODUCTION
This
issue of "Masonry Chronicles" will
highlight the differences
between the masonry design provisions of the
1997 Uniform Building Code (1997 UBC) and
Building Code Requirements for Masonry
Structures:
ACI 530-02/ASCE
5-02/TMS 402-02 by the Masonry Standards
Joint Committee (MSJC Code). The masonry chapter
of the 2003 International Building Code (2003
IBC) references the MSJC Code with some
modifications.
This issue is not intended
to be exhaustive of the differences between the
documents, but only to emphasize major changes
that impact design.
MATERIAL
PROPERTIES
The primary difference in
the material properties between the 1997 UBC and
the MSJC Code is in the calculation of the
values used for the Modulus of Elasticity. In
both the 1997 UBC and the MSJC Code the values
for Em are based on the chord
modulus from a stress value of 5 to 33 percent
of the compressive strength of masonry as shown
in Figure 1.
The Uniform Building Code
calculates the modulus of elasticity for
masonry, Em
,
by the following equation for both clay and
concrete masonry:
Em=750f
'm, 3,000,000 psi max
Section
2106.2.12.1 1997 UBC
In the MSJC CODE, the
calculation of Em
is:
Em =
700f 'm for clay
masonry
Em =
900f 'm for concrete
masonry
Section
1.8.2.2.1 MSJC Code
|
FIGURE
1
|
CALCULATION OF
MODULUS OF
|
|
|
ELASTICITY
(MSJC CODE)
|
SPECIAL
INSPECTION
Special Inspection is not
required by the 1997 Uniform Building Code for
designs developed using Working Stress Design.
However, when Special Inspection is not
used, the code requires a reduction in the
allowable stresses:
"When quality
assurance provisions do not include
requirements for special inspection as
prescribed in Section 1701, the allowable
stresses for masonry in Section 2107 shall be
reduced by one half."
Section
2107.1.2 1997 UBC
Additionally, in the 1997
UBC Special Inspection is required for designs
developed using Strength Design:
"Special
inspection during construction shall be
provided as set forth in Section 1701.5, Item
7."
Section
2108.1.2 1997 UBC
The MSJC Code does not
include any mention of Special Inspection for
either Working Stress or Strength Design. Note,
however, that in Section 1704.5 of the 2003 IBC
two levels of special inspection are specified
depending on the classification of the structure
and the level of occupancy.
WORKING STRESS
DESIGN
STRENGTH
REQUIREMENTS
In the MSJC Code it is
permissible to design structures using the
strength design load combinations with allowable
stresses from working stress design multiplied
by adjustment and strength reduction
factors.
When strength design load
combinations are used, the design strength of a
member, its connections to other members and its
cross sections is given as
f2.5Fa.
Where Fa is calculated
according to the provisions of working stress
design, the strength reduction values,
f,
are as follows:
|
|
f
|
|
Axial
load
|
0.8
|
|
Flexural
compression
|
0.8
|
|
Flexural
tension in unreinforced
masonry
|
0.4
|
|
Shear
|
0.6
|
|
Shear and
tension on anchor bolts
|
|
|
embedded in
masonry
|
0.6
|
Section
2.1.3.3.3 MSJC Code
Note that this section of
the MSJC Code is not allowed by
the 2003 IBC per Section 2107.1.
SHEAR WALL DESIGN
LOADS
In the 1997 UBC, shear
stresses for shear walls in Seismic Zones 3 and
4 must be designed to resist 1.5 times the
forces required by the minimum design lateral
forces. The MSJC Code does not use a similar
multiplier.
ANCHOR
BOLTS
The determination of the
allowable loads in tension for plate, headed,
and bent bar anchor bolts is the same in the
1997 UBC and the MSJC Code. However, text has
been included in the MSJC Code to clarify the
calculation of projected area in partially
grouted masonry:
"That portion
of the projected area falling in an open
cell or core shall be deducted from the value
of Ap
"
Section
2.1.4.2.2.1 MSJC Code
CONCENTRATED
LOADS
The allowable bearing
stress in the 1997 UBC is given by:
"When a member
bears on the full area of a masonry element,
the allowable bearing stress Fbr
is:
Fbr
= 0.26 f 'm
When a member bears
on one third or less of a masonry element,
the allowable bearing stress Fbr
is:
Fbr = 0.38
f 'm
Section
2107.2.10 1997 UBC
The increase is permitted
only when the least dimension between the edges
of the loaded and unloaded areas is one fourth
of the parallel side dimension of the loaded
area. This accounts for confinement of the
bearing area by surrounding masonry, which
increases the bearing capacity of the wall.
Interpolation is allowed between the two
values.
In the MSJC Code, the
allowable bearing stress, Fbr,
is defined as a maximum of 0.25 f
'm However, an increase in
capacity similar to that allowed in the 1997 UBC
is allowed by the application of the
concentrated vertical axial load over an
increased area:
"
but not more than 2A1, where
A2 is the supporting surface wider
than A1 on all sides, or
A2 is the area of the lower base
of the largest frustum of a right pyramid or
cone having A1 as upper base
sloping at 45 degrees from the horizontal and
wholly contained within the
support."
Section
2.1.9.2 MSJC Code
This area increase is
illustrated in Figure 2. Figure 3 illustrates
the differences between the allowable bearing
stresses in the 1997 UBC and the MSJC
Code.
FIGURE 2 BEARING AREA
(MSJC Code)
|
FIGURE
3
|
COMPARISON OF
ALLOWABLE
|
|
|
BEARING
STRESSES
|
STRENGTH
DESIGN
STRENGTH REDUCTION
FACTORS
In the 1997 UBC the
strength reduction factor, f,
for flexure, with or without axial load, is
determined by:
Section
2108.1.4.1.1 1997 UBC
In the MSJC Code
combinations of flexure and axial load use a
constant f
of 0.90.
WALL DESIGN FOR
OUT-OF-PLANE LOADS
PD
effects are considered for out-of-plane wall
design for walls with large relative axial
loads. In the 1997 UBC the axial load level that
determines the use of
PD
effects is 0.04 f 'm. In the
MSJC Code the axial load level for
PD
effects is 0.05 f
'm.
DESIGN SHEAR
STRENGTH
In walls designed to
resist in plane forces a ductile response is
preferred. In the 1997 UBC, ductile behavior of
shear walls is encouraged by increasing the
strength reduction factor:
"Shear:f
= 0.60
The value of f
f
may be 0.80 for
any shear wall when its nominal shear
strength exceeds the shear corresponding to
development of its nominal flexural
strength
"
Section
2108.1.4.3.2 1997 UBC
In the MSJC Code the
ductile response of a shear wall is encouraged
by similarly increasing the design shear
strength of the section:
"The design
shear strength, f
Vn, shall exceed the shear
corresponding to the development of 1.25
times the nominal flexural strength,
Mn, of the member, except that the
nominal shear strength, Vn, need not exceed
2.5 times required shear strength,
Vu."
Section
3.1.3 MSJC Code
NOMINAL SHEAR
STRENGTH
In the 1997 UBC, when the
nominal shear capacity of a shear wall exceeds
the shear corresponding to the development of
its nominal flexural strength, two shear regions
exist. At the base of the wall, the nominal
shear strength is given by:
Vn
= Amv
r
fy
Section
2108.2.5.5 (8-39) 1997 UBC
Note that Vn
= Amv
r
fy,
thus the nominal shear strength at the base of
the wall is equal to the shear strength provided
by the shear reinforcement.
In the MSJC Code, the
masonry strength is included in the calculation
of the nominal shear strength:
Section
3.2.4.1.2 MSJC Code
Where the shear strength
provided by the masonry is given by:
need not be taken greater than 1.0
Section
3.2.4.1.2.1(3-21) MSJC Code
The nominal shear strength
provided by reinforcement in MSJC Code includes
a 0.5 multiplier:
Section
3.2.4.1.2.2 (3-22) MSJC Code
The nominal shear
capacities given by the 1997 UBC and the MSJC
Code at the base of a shear wall are compared in
Figure 4.

|
FIGURE
4
|
COMPARISON OF
NOMINAL
|
|
|
SHEAR
STRENGTH
|
ANCHOR
BOLTS
The calculation of
capacity for bent bar and headed anchor bolts in
the 1997 UBC is as follows and the strength
reduction factor, f, for anchor bolts is a
constant value of 0.80:
Nominal
tensile capacity is the lesser of:

Nominal shear
capacity is the lesser of:

Section
2108.1.5.2 1997 UBC
In the MSJC Code the
capacity of headed anchor bolts is
calculated:
Nominal
tensile capacity is the lesser of:

Nominal shear
capacity is the lesser of:

Section
3.1.6 MSJC Code
The MSJC includes an
additional equation for bent bar anchor bolts
that checks the connection for anchor
pullout:
Nominal
tensile capacity is the lesser of
Eqn (3-4), Eqn
(3-5) and:

Section
3.1.6.2 MSJC Code
The strength reduction
factors for anchor bolts in the MSJC Code vary
depending on the failure mode of the
connection:
|
Masonry
breakout
|
f
=
0.50
|
|
Anchor bolt
steel
|
f
=
0.90
|
|
Anchor
pullout
|
f
=
0.65
|
In addition, text
clarifying the calculation of projected area in
partially grouted masonry similar to that in
Working Stress Design is included in the MSJC
Code.
FLEXURAL DESIGN
ASSUMPTIONS
The maximum usable strain,
emu, at the extreme masonry
compression fiber given by the 1997 UBC is 0.003
for the design of beams, piers, columns and
walls. In the MSJC Code emu is
assumed to be 0.0035 for clay masonry and 0.0025
for concrete masonry.
Also, the strength of the
masonry compressive zone in the 1997 UBC is
calculated using 85% of the masonry compressive
stress and 85% of the area of the compressive
zone. In the 2003 IBC it is calculated as
follows:
"Masonry
stress of 0.80 f¢m
shall be assumed uniformly distributed
over an equivalent compression zone bounded
by edges of the cross section and a straight
line located parallel to the neutral axis at
a distance, a=0.80c, from the fiber of
maximum compressive strain."
Section
3.2.2(g) MSJC Code
The differences between
the 1997 UBC and the MSJC Code are shown in
Figure 5.
Accordingly, the formulas
for the nominal axial compressive strength in
the MSJC Code are:
Equations
3-16 & 3-17 MSJC Code

|
FIGURE
5
|
MASONRY
COMPRESSIVE BLOCK
|
|
|
(a) 1997 UBC
AND
(b) MSJC CODE
|
BOUNDARY ELEMENTS &
THE MAXIMUM REINFORCEMENT RATIO
In Section 2108.2.5.6 of
the 1997 UBC Boundary elements are specified for
walls resisting in plane loads when the
compressive strains in the wall, determined
using factored forces and Rw
equal to 1.5, exceed 0.0015. Also the maximum
reinforcement ratio in the 1997 UBC is given as
0.5r
b.
Note that in this section
the 1997 UBC refers to the obsolete
Rw factor that has been
replaced by the R factor in the 1997 UBC. As
discussed in Design of Reinforced Masonry
Structures by Brandow, Hart and Virdee,
published by the Concrete Masonry Association of
California and Nevada, a comparison of the old
Rw factor and the R
factor (4.5 vs. 6 for masonry bearing walls)
results in using an R of 1.1.
In the MSJC Code no
boundary elements are specified for shear walls,
however, strain is limited by the calculation of
the maximum reinforcement ratio to 0.0025 for
masonry and 5 times yield in the extreme tension
reinforcement when the stress in the tension
reinforcement is assumed to be
1.25fy and the strength of the
compression zone is 80%
f¢m
times 80% of the area of the compressive zone.
CONCLUSIONS
Although the 1997 UBC and
the MSJC Code are similar in approach, there are
some differences in the design equations.
Engineers need to be aware of these differences
in order to use the codes effectively. Future
issues of Masonry Chronicles will investigate
the effect of the differences on design
solutions.
This issue of "Masonry
Chronicles" was written by Melissa Kubischta of
Hart-Weidlinger.
"Masonry Chronicles" is a
publication of the Concrete Masonry Association
of California and Nevada. Reproduction is
expressly prohibited without written permission
from CMACN.
Please contact the
Association Office, with any comments or
suggestions for future issues.
Additional "Masonry
Chronicles" can be seen on the CMACN web site at
http://www.cmacn.org.
PLEASE NOTE: CMACN
E-MAIL ADDRESS CHANGE
The new CMACN e-mail
address is info@cmacn.org
effective April 25, 2003.
ANNOUNCING CMACN
PUBLICATION AVAILABIITY
TYPICAL MASONRY DETAILS
- AUTOCAD 14
(Compatible with Windows
2000 and 2000 XP)
An electronic collection
of masonry details in AutoCAD Release 14 format,
which could be modified by a professional
engineer for incorporation into construction
documents. The collection includes details of
masonry attachment to foundation, concrete
floors, steel framing, glulam beams, and plywood
Web I joists, as well as standard reinforcing
and control joint details.
You may order
publications by sending a check to CMACN at:
6060 Sunrise Vista Drive, Suite 1990, Citrus
Heights, CA 95610 or by credit card faxed to
(916) 722-1819 or by phone to (916)
722-1700.
Cost
$95.00 With Tax and Shipping $112.36
(Out of CA Exclude 7 ¾% sales
tax)
|